Correct at time of publication. Electrical safety laws, codes, exclusion zones and network-operator requirements can change. Always confirm current requirements with the relevant regulator, electricity network operator or asset owner before work begins.
Western Australia
| Powerline | Minimum distance |
|---|
| Up to 1 kV, insulated | 0.5 m |
| Up to 1 kV, uninsulated | 1.0 m |
| Above 1 kV to 33 kV | 3.0 m |
| Above 33 kV | 6.0 m |
Queensland
| Powerline | Minimum distance |
|---|
| Up to 132 kV | 3.0 m |
| Above 132 kV to 330 kV | 6.0 m |
| Above 330 kV | 8.0 m |
New South Wales
For conductive scaffolding, maintain a minimum 4.0 m approach distance from overhead powerlines up to and including 33 kV. For higher voltages, consult the electricity network operator.
Australian Capital Territory
| Scaffold type | Minimum distance |
|---|
| Metal scaffold | 4.0 m |
| Timber scaffold | 1.5 m |
Victoria
| Powerline | Open area | With qualified spotter |
|---|
| Pole-mounted lines up to 66 kV | 6.4 m | 3.0 m |
| Tower-mounted lines above 66 kV | 10.0 m | 8.0 m |
Tasmania
| Powerline | Open area | With safety observer |
|---|
| Up to and including 133 kV | 6.4 m | 3.0 m |
| Above 133 kV | 10.0 m | 8.0 m |
South Australia
| Powerline | Without spotter | With spotter |
|---|
| Pole-mounted lines | 6.4 m | 3.0 m |
| Tower-mounted lines | 10.0 m | 8.0 m |
Northern Territory
Keep scaffolding outside the applicable electrical no-go zone. Where work may enter the no-go zone, confirm the current requirements and obtain any required permit or authority from the powerline asset owner before starting.
VOC reminder
If the voltage or required clearance is uncertain, stop and confirm it with the electricity network operator or asset owner before proceeding.